|
||||
|
|
We can supply and install a vast range of fire detection equipment from a simple batteryoperated smoke detector to a full fire detection system. All are fire systems are BS5389 Complient and are certified on
installation. We cover all the following clasification of detection systems: System Classifications Type P systems are automatically
activated fire detection systems designed to protect property.
Type P1 Fire system installed throughout building. Type P2 Fire system only installed in a defined part of the building. Type L systems are automatically activated fire detection systems designed to protect life. These systems are then sub-divided into: Type L1 Fire system installed throughout building. Type L2 Fire system only installed in a defined part of the building. Type L3 Fire system only installed for the protection of escape routes. Type M systems encompass all manually activated fire systems.
We can also arrange for a full maintence plan for your fire system to comply with BS5839 TESTING AND
MAINTENANCE
We can arrange a maintenance package to suit almost any system, and to comply with BS5839 a guide of what needs to be tested and when is listed below. DAILY INSPECTION Check that the Charger On indicator shows. Inspect for any fault indicator showing or sounder operating. Inform the designated responsible person of any fault. WEEKLY TEST Ensure that all indicators show by resetting according to the instructions provided with the panel and check that the internal sounder operates. Operate a call point or detector to test the system. Check that the sounders operate. Reset the fire alarm panel. Each week choose a different zone in rotation, so that way all call points are tested in rotation. Check all call points and detectors and ensure that none are obstructed in any way. Enter results of tests into log book. SIX MONTHLY TEST Check all previous log book entries and clarify that any remedial action has been taken. Check the battery and its connections. Operate a call point or detector in each zone to test the fire alarm as per above. Remove mains supply and check that the battery is capable of supplying the alarm sounders. ANNUAL TEST As per above. Additionally test all detectors and call points and check for operation. EVERY 2 - 3 YEARS Clean smoke detectors to ensure correct operation and freedom from false alarms. Special equipment is required for cleaning smoke detectors. EVERY 4 YEARS Replace sealed lead acid batteries. If the operating temperature exceeds 25oC continuously, then the battery may need to be replaced sooner. |
|||
| Web design software by PersonalWebKit | ||||